PVC 3 & 4 Core Round Submersible Pump Cable

 

  • Conductor:High purity electrolytic grade bright annealed flexible bunched bare, copper conductor according to international standards like IS 8130, BS 6360, IEC 228 & VDE 0295.
  • Insulation:Specially developed dielectric grade PVC Compound impervious to water, oils, grease etc.
  • Sheath:Sheathing by High abrasion resistant tough & flexible PVC Compound
  • IS 694, BS 6500, IEC 60227, CEI 20-20, VDE 0281, SABS 1574, AS 3191, AS/NZS 5000.1, HD 21.1, NF C 32-201, French Standard 32-102-1
  • 450/ 750 V, 600/ 1000 V, 650/1100 V
  • 3000 V
  • -150C to 700 C
  • H07VV-F, FROR, S07VV-F, H07VV-K, A07VV-F
Core colors (For Asian, African Markets) (For European Markets) New colour code for European Markets
3 core  Red ,Yellow, Blue  Black, Blue, Brown  Brown, Black, Grey
4 core  Red ,Yellow, Blue, Green  Black, Blue, Brown, Green  4G: Brown, Black, Grey, Green/Yellow OR
4 C : Brown, Black, Grey, Blue
Sheath color: Choice of  Black  or Blue Choice of  Black  or Blue Choice of  Black  or Blue
   
   

PVC 3 core Round Submerisble Cable

Nos. of Cores
X Size
sq.mm
No./
size of
wire
no./mm
Insulation
thickness
(nom.)
mm
Sheath
thickness (nom.)
mm
Overall dimensio
ns
(approx.) mm
Conductor
resistance
at 20° C
(max.) ohm/km
Current
carrying
capacity at
40° C amps.
3 x 1.5 22/.3 0.6 0.9 8.6 12.1 14
3 x 2.5 36/.3 0.7 1.0 9.8 7.41 18
3 x 4 56/.3 0.8 1.0 11.5 4.95 26
3 x 6 84/.3 0.8 1.1 13.3 3.3 31
3 x 10 140/.3 1 1.2 16.5 1.91 42
3 x 16 226/.3 1 1.3 19.7 1.21 57
3 x 25 354/.3 1.2 1.5 24.0 0.78 72
3 x 35 495/.3 1.2 1.6 27.0 0.554 90
3 x 50 703/.3 1.4 1.7 31.3 0.386 115
3 x 70 360/.5 1.4 2.0 37.3 0.272 143
3 x 95 475/.5 1.6 2.0 43.3 0.206 165

PVC 4 core Round Submerisble Cable

Area (nom)
sq.mm
Nos./
size of
wire
no./mm
Insulation
thickness
(nom.)
mm
Sheath thickness
(nom.)
mm
Overall dimensions
(approx.)
mm
Conductor
resistance
at 20° C
(max.) ohm/km
Current
carrying
capacity at
40° C amps.
4 x 1.5 22/.3 0.6 0.9 9.4 12.1 14
4 x 2.5 36/.3 0.7 1.0 10.8 7.41 18
4 x 4 56/.3 0.8 1.0 12.7 4.95 26
4 x 6 84/.3 0.8 1.2 14.8 3.3 31
4 x 10 140/.3 1 1.3 18.4 1.91 42
4 x 16 226/.3 1 1.4 21.8 1.21 57
4 x 25 354/.3 1.2 1.6 26.8 0.78 72
4 x 35 495/.3 1.2 1.7 30.2 0.554 90
4 x 50 703/.3 1.4 1.8 34.9 0.386 115
4 x 70 360/.5 1.4 2.0 41.4 0.272 143
4 x 95 475/.5 1.6 2.2 48.1 0.206 165


Note:
Insulation thickness, Sheath thickness and overall dimensions are nominal values. The number of wires is approximate and strand diameter is nominal; they shall be such as to satisfy the requirements of conductor resistance as per IS 8130/1984, BS-6360, IEC-60228 & VDE-0295.